Full specification
Monitoring: Input and Breaker current monitoring. Local highvisibility LED display. Input and per Phase power monitoringavailable via VLC using the Vertiv rPDU Scanner app.
Monitoring Level 1: Phase (A) Monitoring (kWh, W, VA, PF, V, A)Power Measurements Compliant with ANSI C12.1 and IEC62053-21 at 1% Accuracy Class Requirements
Monitoring Level 2: Circuit / Breaker Monitoring (A)Circuit/Breaker Current Measurements Independently Testedand Verified at 2% Accuracy
VLC Support: Yes
Quantity Of Inputs: 1
Voltage: 230V
Current: 32A
VA per Input (Load Capacity): 7.3kW
Frequency: 50/60Hz
Over Current Protection: (2) 16A Single Pole Magnetic Breakers
Switch: Breaker/Switch Combination
Scrolling / Rotatable Digital Display: Yes
Power Cable Wire Gauge: 4mm2
Power Cable Length: 3m
Power Entry Location: Bottom Front
Plug Type: IEC60309 2P+E, 32A, 250V, Splash proof IP44
Combined Total Receptacle/Socket Quantity: 24
Receptacle/Socket Type #1: U-Lock IEC C13
Quantity: 20
Quantity per Breaker: 10
U-Lock color: 2 Circuit = Orange, Green
Maximum Output per Receptacle/Socket: 10A
Voltage per Receptacle/Socket: 230V
Receptacle/Socket Type #2: U-Lock IEC C19